HomeMy WebLinkAboutBLDG PERMIT #9243 (HVAC Load Analysis) k
Beach Wave
HVAC Load Analysis
for
Beach Wave
8801 Astronaut Blvd.
Cape Caneveral, FL
tole)014 : :.1 rcH\f
AC COMMERCIAL
• HVAC LOADS
•
e°aa wa s a ei fly`
4„ • „Gcft
:0 0 82
•. _S AT 1qo
•
Fre
•
yo`u r .I”1 Aa`►+°
�7�'aa�aoga64�o°
Prepared By:
Eric J. Svoboda, PE
Fort Pierce Engineering, Inc.
315 South 7th Street
Fort Pierce, FL 34950
772-672-4636
Thursday, July 26, 2012
Elite Software Development,Inc.
Chvac Full CQmrc��l'�V AGoads�C,a�lculation Program I � * Beach Wave
�y c
t'nxt� ., c - - Page 2
1 Building Summary Loads
Building peaks in August at 4pm.
i. v. 3 t , 1A� ''" '''f'' enk-Y*r y { SyS.;mt"�'v''4'.i�+ ; ••'Sen Net %Net
•Bldg Load �,,., t�� i�� �f l • Gain
Ii �'- '., `ICIOan,: # . .ss-al ls,',�� -T" .e;r a.,•Gain Gain 'Gain n
Descnptrons�•� - . . .
Roof 15,177 50,084 20 83 0 60,234 60.234 10 0
Wall 5,429 17,020 7 08 0 13,065 13.065 2 18
Glass
2,711 74,254 30.89 0 110,610 110,610 18 45 Floor Slab 407 8,327 3.46 0 0 0 0 00
Skin Loads 149,686 62.27 0 183,908 183,908 30.67
Lighting 30,354 0 0.00 0 103.572 103,572 17 27
Equipment 15,852 0 0.00 0 54,089 54.089 9 02
People 238 0 0.00 47,613 59,517 107,130 17.87
Partition 2,000 1,640 0.68 0 1,640 1,640 0 27
Cool. Pret0 0 0.00 0 0 0 0 00
.
Heat. Prat. 0 0 0.00 0 0 0 0.00
Cool. Vent. 2,500 0 0.00 89,838 54,980 144,818 24 15
5
Heat. Vent. 2,500 89,068 37.05 0 0 0
0 0 0.00 0 0 0 0 00
Cool. lnfil.
Heat 'Mil 0 0 0.00 0 0 0 0.00
Draw-Thru Fan 0 0 0.00 0 4,492 4,492 0.75
0 0 0.00 0 0 0 0.00
Blow-Thru Fan 0 0 0.00
Reserve Cap. 0 0 0.00 0 0 0 0.00
Reheat Cap. 0 0 0.00 0 0 0 0.00
SupplyDuct 0 0 0.00 0 0 0 00
Return Duct 0 0 0.00 0 0.00 0 0 0 0 00
Misc. Supply 0 0 0 .00 0 0 0 0 00
Misc. Return
Building Totals 240,393 100.00 137,451 462,198 599,649 100 00
rig t ..� r ,a�.S•,,,,.� M ;^let %Net
B u l l d l n r � : 4,, 3 1 7 f, . 0 'P /� il:,} ii 4 9', 5 r "'2 r p fit
9-i v. �,.n t 7 �,� `, 'R Gatn" Gain
(Summary "Yx' _ ,9SS.,.• v. .. Losse �.,.� ,: ...Gain:. ,.� a
Ventilation 89,068 37.05 89,838 54,9800 144,8188 2415
5
Infiltration 0 0.00 0
Pretreated Air
0 0.00 0 0 0 000
450,34
Zone Loads 151,326 62.95 47,613 402,726 0
0 0 50 75.1 10
Plenum Loads 0 0.00 0
Fan& Duct Loads 0
4,492
Building Totals 240,393 0.00 0 4,492
gur�� 100.00 137,451 462,198 599.649 100 00
[Check Flrs on a 21° TD): 18,754 CFM 0.75
Total Building Supply
Total Building Vent. Air(13 33% of Supply): 2,500 CFM
Total Conditioned Air Space: 15,177 Sq.ft
Supply Air Per Unit Area: 1.2357 CFM/Sq.ft
Sq.ft/Ton
Area Per Cooling Capacity. 0.0 303.77 Tons/Sq.fton
Cooling Capacity Per Area. .0033 Btuh/Sq.ft
Heating Capacity Per Area:
Btuh
Total Heating Required With Outside Air: 240,393493 Tons
Total Cooling Required With Outside Air:
-- -- --"-------_-_-- Thursday.July 26.2012. 01 40 PM
Z\ Beach wave Heat Load 2 CHV
Chvac-Full Commercial HVAC Loads Calculation Program _ Elite Software Development,Inc.
• Beach Wave•
`. . Iii• ., :
_
Page
Air Handler #1 AHU 1 Thru 4 - Summary Loads
Zn 14eVaiitiad �x<>�s a ."`4 r ' .A 1# . 1k.1143ss eGanzK
a�tG,ain Htg.0.A. CIg.O.A.
No Zone R f' . f•` � .;r'.. . Mme T.A. t,M//S ft. r,, CFM "M•• :,-...4: . "Vliri 4"4-4'CFM A Q.CFM
I r x i4- . s�.r r t q . � q
1 Main Retail 10,400 96,275 270,459 30,000 Direct Direct
4pm August 150 4,459 11,835 0 1,400 1.400
208,000 0.43 1.14 0 1.400 1 400
Zone Peak Totals: 10,400 96,275 270,459 30,000 1 400
Total Zones: 1 150 4,459 11,835 0 1.400
Unique Zones: 1 208,000 0.43 1.14 0 1,400 1.400
I
•
•
•
I
•
Thursday,July 26. 2012,01.x0
Z'.\...\Beach Wave Heat Load 2.CHV
_.__— --- -—
Chvac-Full Commercial HVAC Loads Calculation Program . aElite Software Development,Inc.
Beach Wave
__Page 4
Air Handler#1 - AHU 1 Thru 4 - Total Load Summary___
Air Handler Description: AHU 1 Thru 4 Constant Volume - Proportion
Supply Air Fan: Draw-Thru with program estimated horsepower of 1.12 HP
Fan Input: 0% motor and fan efficiency with 0 in. water across the fan
Sensible Heat Ratio: 0.90 --- This system occurs 1 time(s) in the building -
Air System Peak Time: 4pm in August.
Outdoor Conditions: Clg: 95° DB, 78° WB, 118.31 grains, Htg: 42° DB
Indoor Conditions: Clg: 75° DB, 50% RH, Htg: 75° DB
Summer: Ventilation controls outside air, Winter: Ventilation controls outside air.
Zone Space sensible loss: 96,275 Btuh 0 CFM
Infiltration sensible loss: 0 Btuh
Outside Air sensible loss: 49,878 Btuh 1,400 CFM
Supply Duct sensible loss: 0 Btuh
Return Duct sensible loss: 0 Btuh
Return Plenum sensible loss: 0 Btuh 146,153 Btuh
Total System sensible loss:
Heating Supply Air: 96,275 /(1.000 X 1.08 X 20) _
4,459 CFM
Winter Vent Outside Air (31.4% of supply) = 1,400 CFM
Zone space sensible gain: 270,459 Btuh
Infiltration sensible gain: 0 Btuh
Draw-thru fan sensible gain: 2,834 Btuh
Supply duct sensible gain: 0 Btuh
Reserve sensible gain: 0 Btuh
I
Total sensible gain on supply side of coil: 273,293 Btuh
Cooling Supply Air: 273,293/(1.000 X 1.1 X 21) = 11,835 CFM
Summer Vent Outside Air (11.8%of supply) = 1,400 CFM
Return duct sensible gain: 0 Btuh
Return plenum sensible gain: 0 Btuh
Outside air sensible gain: 30,789 Btuh 1,400 CFM
Blow-thru fan sensible gain: 0 Btuh
30,789 Btuh
Total sensible gain on return side of coil: 304,082 Btuh
Total sensible gain on air handling system:
Zone space latent gain: 30,000 Btuh
Infiltration latent gain: 0 Btuh
Outside air latent gain: 50,309 Btuh Btuh
Total latent gain on air handling system: 80,309380,30Btuh
Total system sensible and latent gain:
Check,
Fi-gures4iW: . A,.- i ) iiti mdi 04 T
Nt 0tN* .Total Air Handler Supply Air(based on a 21° TD): 11,835 CFM
Total Air Handler Vent. Air(11.83% of Supply): 1,400 CFM
Total Conditioned Air Space: 10,400 Sq.ft
Supply Air Per Unit Area: 1.1380 CFM/Sq.ft
Area Per Cooling Capacity: 324.7 Sq.ft/Ton
Cooling Capacity Per Area: 0.0031 Tons/Sq.ft
Heating Capacity Per Area. 14.05 Btuh/Sq.ft
Total Heating Required With Outside Air: 146,153 Btuh
Total Cooling Required With Outside Air: 32.03 Tons
-- - ----- ----- Thursday,July 26,2012.01 40
Z.1...\Beach Wave Heat Load 2.CHV
•
•
Chvac Full Commercial HVAC Loads Calculation Program (11
Beach Wave
:' Elite Software Development,Inc.
,d rYi4 �,*i 1�g�.,�''t 3 41r I
Page 5
Air Handler#2 - AHU 5 - Summary Loads
Zn Description '. Area. '- Htg.Loss Sen.Gain Lat.Gain Htg.O.A. CIg.O.A.
No Zone Peak Time Fe ople��� Htg.CFM CIg CFM , S.Exh Req.CFM .Req.CFM
- VoIume ,o<.,CFM/Sgft CFM/S.ft" .- W.Exh Act.CFM _ Act.CFM
2 Arcade 1,892 16,268 43,362 6,000 Direct Direct
11am August 30 753 1,875 0 322 322
37,840 0.40 0.99 0 330 332
3 Men 180 2,091 3,973 240 Direct Direct
4pm August 1 97 172 0 31 31
3,600 0.54 0.95 0 42 30
4 Women 180 594 2,938 240 Direct Direct
2pm August 1 28 127 0 31 31
3,600 0.15 0.71 0 12 23
5 Corridor 100 746 1,913 133 Direct Direct
3pm August 1 35 83 0 17 17
2,000 0.35 0.83 0 15 15
Zone Peak Totals: 2,352 19,699 52,185 6.613 400 400
Total Zones: 4 33 912 2,257 0 400 400
Unique Zones: 4 47,040 0.39 0.96 0
i
•
i
i
Thursday.July 26. 2012 01 40
Z1 \Beach Wave Heat Load 2.CHV
•
Software Development, nc.
Chvac-Full Commercial HVAC Loads Calculation Program Elite Beach Wave
Page 6
;[Air Handler #2 - AHU 5 - Total Load Summary _.
Air Handler Description: AHU 5 Constant Volume - Proportion
Supply Air Fan: Draw-Thru with program estimated horsepower of 0.21 HP
Fan Input: 0% motor and fan efficiency with 0 in. water across the fan
Sensible Heat Ratio: 0.89 --- This system occurs 1 time(s) in the building -
Air System Peak Time: 3pm in August.
Outdoor Conditions: Clg: 95° DB, 78° WB, 117.53 grains, Htg: 42° DB
Indoor Conditions: Clg: 75° DB, 50% RH, Htg: 75° DB
Summer: Ventilation controls outside air, Winter: Ventilation controls outside air.
Zone Space sensible loss: 19,699 Btuh 0 CFM
Infiltration sensible loss: 0 Btuh
Outside Air sensible loss: 14,251 Btuh 400 CFM
Supply Duct sensible loss: 0 Btuh
Return Duct sensible loss: 0 Btuh
Return Plenum sensible loss: 0 Btuh 33.949 Btuh
Total System sensible loss:
Heating Supply Air: 19,699/(1.000 X 1.08 X 20) = 912 CFM
Winter Vent Outside Air(43.8%of supply) = 400 CFM
Zone space sensible gain: 51,576 Btuh
Infiltration sensible gain: 0 Btuh
Draw-thru fan sensible gain: 541 Btuh
Supply duct sensible gain: 0 Btuh
Reserve sensible gain: 0 Btuh
Total sensible gain on supply side of coil: 52,117 Btuh
Cooling Supply Air: 52,117/(1.000 X 1.1 X 21) = 2,257 CFM
Summer Vent Outside Air(17.7% of supply) = 400 CFM
Return duct sensible gain: 0 Btuh
Return plenum sensible gain: 0 Btuh 400 CFM
Outside air sensible gain: 8,797 Btuh
Blow-thru fan sensible gain: 0 Btuh
8,797 Btuh
Total sensible gain on return side of coil: 68,797 Btuh
Total sensible gain on air handling system:
Zone space latent gain: 6,613 Btuh
Infiltration latent gain: 0 Btuh
Outside air latent gain: 14,374 Btuh
Total latent gain on air handling system: 20,987 Btuh
81,9017 7 Btuh
Total system sensible and latent gain: - . t
j CheckFigures) ,F ain :**Watr rv*u 5. ..:; . . ti,,r X ,u4, it,% 4.V4,.t.,..,
.,
Total Air Handler Supply Air (based on a 21° TD): 2,257 CFM
Total Air Handler Vent. Air(17.72% of Supply): 400 CFM
Total Conditioned Air Space: 2,352 Sq.ft
Supply Air Per Unit Area: 0.9596 CFM/Sq.ft
Area Per Cooling Capacity: 344.6 Sq.ft/Ton
Tons/Sq.ft
Cooling Capacity Per Area: 0.002914.43 Btuh/Sq.ft
Heating Capacity Per Area:
Total Heating Required With Outside Air: 33,949 Btuh
Total Cooling Required With Outside Air:
6.83 Tons
--- Thursday.July 26. 2012, 01 40 PM
Z\ tiBeach Wave Neat toad 2.CHV
_ -
ChElite Software Development,Inc.vac-Full Commercial HVAC Loads Calculation Program 3-. 1 _ .. Beach Wave
:�L1E Page 7
------------
Air Handler #3 - AHU 6 - Summary Loads
Zn Description Area Htg.Loss Sen.Gain Lat:Gain Htg.O.A. CIg.O.A.
No Zone Peak Time "FA Peopie� -Htg.CFM`. CIg.CFM S:Exh Req.CFM Req.CFM
Volum ,c'.CFM/Sgft_ CFM/Sgft - W.Exh Act.CFM_.— Act.CFM
6 Future Tenant 2 1,425 11,993 43,961 8,000 D1rect 400 D'400
rect
8am August 40 555 1,835 0
28,500 0.39 1.29 0 400 400
Zone Peak Totals: 1,425 11,993 43,961 8,000 400 400
Total Zones: 1 40 555 1,835 0
Unique Zones: 1 28,500 0.39
1.29 0 400 400
.
----- -- -----
- — -- — — Thursday.July 26 2012. 01 40
Z:1...1Beach Wave Heat Load 2.CHV
•
Chvac•Full Coi ime a HVAC' . ats 71 ti 'Pro 4'.17'H":":1':,ma ` '^ Vf :'41 x' e , . „••Elite Software Development,Inc.'
1 ,+ Beach Wave
,,,,..-10-0.4 ,•:41$0,4u,,,..44,....-.444.41,,,...,
cwr �I +�„' v IK Page 8
Air Handler #3-AHU 6 - Total Load Summary
Air Handler Description: AHU 6 Constant Volume - Proportion
Supply Air Fan: Draw-Thru with program estimated horsepower of 0.17 HP
Fan Input: 0% motor and fan efficiency with 0 in. water across the fan
Sensible Heat Ratio: 0.85 ---This system occurs 1 time(s) in the building -
Air System Peak Time: 1pm in August.
Outdoor Conditions: CIg: 93° DB, 78°WB, 120.41 grains. Htg: 42° DB
Indoor Conditions: CIg: 75° DB, 50% RH, Htg: 75° DB
Because of the diversity in zone, plenum and ventilation loads, the zone sensible peak time in August at 8am is different
from the total system peak time, hence the air system CFM was computed using a zone sensible load of 43,961.
Summer: Ventilation controls outside air, Winter: Ventilation controls outside air.
Zone Space sensible loss: 11,993 Btuh
Infiltration sensible loss: 0 Btuh 0 CFM
Outside Air sensible loss:
14,251 Btuh 400 CFM
Supply Duct sensible loss: 0 Btuh
Return Duct sensible loss: 0 Btuh
Return Plenum sensible loss: 0 Btuh
26,244 Btuh
Total System sensible loss:
Heating Supply Air: 11,993/ (1.000 X 1.08 X 20) = 555 CFM
Winter Vent Outside Air (72.0% of supply) _
400 CFM
Zone space sensible gain: 41,560 Btuh
Infiltration sensible gain: 0 Btuh
Draw-thru fan sensible gain: 440 Btuh
Supply duct sensible gain: 0 Btuh
I Reserve sensible gain: 0 Btuh 42,000 Btuh
Total sensible gain on supply side of coil:
Air: 44,401 / (1.000 X 1.1 X 22) = 1,835 CFM
Cooling Supply
Summer Vent Outside Air (21.8% of supply) = 400 CFM
Return duct sensible gain: 0 Btuh
Return plenum sensible gain: 0 Btuh
Btuh 400 CFM
Outside air sensible gain: 7,9170 Btuh
Blow-thru fan sensible gain: 7.917 Btuh
Total sensible gain on return side of coil: 47.917 Btuh
Total sensible gain on air handling system:
Zone space latent gain: 8,000 Btuh
Infiltration latent gain: 0 Btuh
Outside air latent gain: 15,264 Btuh 23,264 Btuh
Total latent gain on air handling system: 73,181 Btuh
Total system sensible and latent gain: _.
I Check Rs Ures3 ,{ n. *c.; �... 01,835 CFM
Total Air Handler Supply Air (based on a 22° TD): 400 CFM
Total Air Handler Vent. Air(21.79% of Supply)'
1,425 Sq.ft
Total Conditioned Air Space: 1, C
Supply Air Per Unit Area: 1.28800 CFM/Sq.ft
FM/ on
Area Per Cooling Capacity: 0.0043233. Tons/Sq.ftftJTo
Cooling Capacity Per Area: 43 Btuh/Sq.ft
Heating Capacity Per Area
26,244 Btuh
Total Heating Required With Outside Air: 6.14 Tons
Total Cooling Required With Outside Air:
Thursday.July 26. 2012 01 40 PM
Z1 \Beach Wave Heat Load 2.CHV
9 --
Elite oftware Development,Inc.
--- _ - S
Chvac-Full Commercial HVAC Loads Calculation Program ill
Beach Wave
_ -- Page 9
Air Handle r #4 - AHU 7 - Summary Loads
•
..... -tea -, a- �, ---
- t 3 ' g
Zn Description r �� [ -,t ,•Htg Loss Sen.Galn ;j, ain Htg:O.A. CI
No Zone Peak Time ` •Peopfe', :Ntg CFM CIg.CFM S.Exh Req.CFM Req.CFM
11 Vo c. e CFM/Sgft CFM/Sgft .. W,Exh Act CFM Act.CFM
7 Future Tenant 1 1,000 23,359 61,494 3,000 Direct Direct
gam August 15 1,082 2,827 0 300 300
20,000 1.08 2.83 0 300 300
Zone Peak Totals 1,000 23,359 61,494 3,000 300 300
Total Zones: 1 15 1.082 2.827 0 300
Unique Zones. 1 20,000 1.08 2.83 0 300
I
4
I
9
I
4
4
1
•
•
•
•
— Thursday.July 26,2012.01:40 PM
Z:\ .\Beach Wave Heat Load 2.CHV
' Chvac-Full Commercial HVAC Loads Calculation Program • • Elite Software Development,Inc.
Beach Wave
_ Page 10
Air Handler #4 -AHU 7-.Total Load Summary
Air Handler Description: AHU 7 Constant Volume - Proportion
Supply Air Fan: Draw-Thru with program estimated horsepower of 0.27 HP
Fan Input: 0% motor and fan efficiency with 0 in. water across the fan
Sensible Heat Ratio: 0.95 ---This system occurs 1 time(s) in the building -
Air System Peak Time: 9am in August.
Outdoor Conditions: Clg: 84° DB, 75° WB, 119.82 grains, Htg: 42° DB
Indoor Conditions: Clg: 75° DB, 50% RH, Htg: 75° DB
Summer: Ventilation controls outside air, Winter: Ventilation controls outside air.
Zone Space sensible loss: 23,359 Btuh 0 CFM
Infiltration sensible loss: 0 Btuh
Outside Air sensible loss: 10,688 Btuh 300 CFM
Supply Duct sensible loss: 0 Btuh
Return Duct sensible loss: 0 Btuh
Return Plenum sensible loss: 0 Btuh
Total System sensible loss: 34,047 Btuh
Heating Supply Air: 23,359/(1.000 X 1.08 X 20) = 1,082 CFM
Winter Vent Outside Air (27.7% of supply) = 300 CFM
Zone space sensible gain: 61,494 Btuh
Infiltration sensible gain: 0 Btuh
Draw-thru fan sensible gain: 677 Btuh
Supply duct sensible gain: 0 Btuh
Reserve sensible gain: 0 Btuh
62,171 Btuh
Total sensible gain on supply side of coil:
Cooling Supply Air: 62,171 / (1.000 X 1.1 X 20) = 2,827 CFM
Summer Vent Outside Air(10.6% of supply) = 300 CFM
Return duct sensible gain: 0 Btuh
Return plenum sensible gain: 0 Btuh
Outside air sensible gain:
2,969 Btuh 300 CFM
Blow-thru fan sensible gain: 0 Btuh Btuh
Total sensible gain on return side of coil: 6 2,9692, 69 Btuh
Total sensible gain on air handling system:
Zone space latent gain: 3,000 Btuh
Infiltration latent gain: 0 Btuh
Outside air latent gain: 10,574 Btuh 3,574 Btuh
Total latent gain on air handling system: 1 13,574 Btuh
Total system sensible and latent gain:
gat � 3 ext Y- �t�.td 'Ft}ly2l
� ,.a ,,�,��,,. �...�� .. 4�_. 2,827 CFM —
�Check.Faguresa� �;� �' � ,.
Total Air Handler Supply Air (based on a 20° TD): 300 CFM
Total Air Handler Vent. Air (10.61% of Supply).
Sq.ft
Total Conditioned Air Space: 2.1,000000 C
Supply Air Per Unit Area: 152.5 CFM/Sq.ft
FM/ on
Area Per Cooling Capacity: 152. Tons/ on
Cooling Capacity Per Area: 0.006665 ons Sq.ft
q.ft
Heating Capacity Per Area:
Total Heating Required With Outside Air: 34,047 Btuh6.57 Tons
Total Cooling Required With Outside Air:
_ -- -- Thursday.July 26, 2012. 01 40
PM
Z.1 \Beach Wave Heat Load 2.CHV