HomeMy WebLinkAbout8801 Astronaut Blvd (7)EXISTING UPRIGHT SPRINKLFR
TO REMAIN TYPICAL
REMOVE EXISTING UPRIGHT PRINKLER
AND 1 BUSHING ARMOVER TO NEW
PENDENT SPRINKLER AS SHOWN
TYPICAL
FLOOR PLAN - FIDE FROTECTION rb/
?4 I �
SCALE 1/8 =1 —0
WATER SUPPLY
DESIGN CF I iERIA
HYDRAULICALLY DESIGNED SYSTEM
TYPES OF SPRINKLERS
NO
DATE
REVISION DESCPIPTION
BY
FLOW TEST
FIRE PUMP
SYSTEM NO
LOCATION
SYMBOLS
SI N
QUAN
ORIF
TEMP
MAKE & MODEL
TYPE
FINISH
ESC
0
9 25 13
SUBMITTED FOR APPROVAL
CJL
DATE OF TEST
RATED CAPACITY
HAZARD
NO OF SPRINKLERS
RA1414
6
56
155
RELIABLE F1FR
SSP
WHITE
RECESSED
TIME OF TEST
RATED PRESSURE
SPACING
ij
T
DENSITY
®
RA1414
10
56
200
RELIABLE F1FR
SSP
WHITE
RECESSED
STATIC PRESSURE
PUMP TYPE
K FACTOR
T
DESIGN AREA
C
R5714
1
56
200
RELIABLE F3QR
DRY SSP
WI -'I FE
2 PIECE DP
RESIDUAL PRESSURE
GALLONS FLOWING
WELL PUMP
GPM AVAILABLE
INSIDE HOSE
OUTSIDE HOSE
��i
_
GPM DISCHARGE
RESIDUAL PSI AT
CITY CONNECTION
17
HEADS
THIS
SHEET
TESTED BY
PSI AVAILABLE
RACK GPM
STEEL ANGLE
TOP Br -AM CLAMP
ZINC THREADED ROD
HANGER RING
#1 �ANGER DETAIL
NOT TO SGALE
STEEL PURLIN
HAMMY SUPER SCREW
SWDR 1
3/8 ZINC A T R
SEE PLAN FOR LENGTH
BANGER RINu — SEE
ALAN FOR SIZES
kANGER DETAIL
NOT TO SCALE
City of CW CaLavemil
PERMITTED FOR CONSTR�'DRt
PERMIT No „ / �_ _ 1 01 1 i
REVIEWED lC1�3
Review vl this p an os not �Aiii raze vto
any local state or feurai code c dttt�ttces or 941
rre t:tor
REVIEWED FOR COMPLIANCE
This approval shall not be construed as authority to
violate cancel alter or set aside any pro rasions of
any state or local governing authority regulating
constructon or the performance of construction
All provisions of law and ordinances go ferning
this t jpe of work must be complied with whetner
herein specified or not Nor shall approval of these
plans prevent the Fire Department from requiring
additional specific i! is equinng correctign
tri pl fo / r ��./`v�,�Gi�
DATElans Examiner
t�
i
3060 Cavel Street
West Melbourne Florida 32904
Ph 3z1-508-2767
coiemanflre@cfl rr com
GENERAL NOTES
1 FIRE PROTECTION SYSTEM DESIGN MATERIALS
INSTALLATION AND TESTING SHALL COMPLY WITH
NEPA 13 (2007 ED) AND ALL APPLICABLE STATE
AND LOCAL CODES
2 SPRINKLER HEADS ARE NOT REQUIRED TO BE
CENTERED IN ACOUSTICAL CEILING TILE
3 ANY AND ALL PENETRATIONS IN FIRE / SMOKE
WALLS SHALL BE FIRE AND SMOKE STOPPED
WITH A LISTED ASSEMBLY
4 ALL PRODUCTS PIPING AND EQUIPMENT USED
FOR FIRE PROTECTION WORK SHOWN ON THESE
DRAWINGS SHALL BE UL LISTED AND BEAR
SUCH MARKINGS SEE MATERIAL SUBMITTAL
DATA FOR PRODUCTS TO BE USED
5 ANY SPRINKLER HEADS TO BE INSTALLED IN
HARD CEILINGS SHALL BE PROTECTED BY A
REMOVABLE HEAD COVER TO ENSURE HEAD 1S
NOT DAMAGED DURING CEILING FINISHING
PROCESS
6 HANGER SPACING AND INSTALLATION SHALL
CONFORM WITH NEPA 13 (2007 ED)
7 ALL THREAD ROD SHALL BE ZINC PLATED
8 MATERIAL OF INTERNATIONAL ORIGIN MAY BE
USED
9 NO PAINTING WIRING OR PROVIDING OF FIRE
EXTINGUISHERS IS REQUIRED OF THIS
CONTRACTOR
10 ALL OUTLETS SHALL BE SHOP WELDED TAPE AND
PIPE DOPE SHALL BE USED AT ALL WELDED
OUTLETS
1 PIPE JOINT COMPOUND SHALL BE USED AT ALL
THREADED CONVECTIONS
12 ALL GROOVED PIPING SHALL BE BLACK SCP 10
PIPE UNLESS OTHERWISE NOTED
13 ALL THREADED PIPING SHALL BE BLACK SCH 40
UNLESS OTHERWISE NOTED
14 ALL GROOVED MAINS ARE SHOWN AS CUT
DIMENSIONS ALL TL- RE<aDED LINES ARE SHOWN
AS CUT DIMENSIONS
15 TYPE OF CONSTRUCTION STEEL PURLIN
16 DESIGN FOR EXISTING BUILDING IS BASED ON
AN ORDINARY HAZARD GROUP 2 OCCUPANCY
MERCANTILE PIPE SIZING IS BASED ON
PROVIDING 20 GPM OVER THE ENTIRE AREA
INCLUDING THE MOST REMOTE 1500 SQ FT 250
GPM COMBINED HOSE ALLOWANCE HAS BEEN
ADDED AT THE CONNECTION TO THE NEAREST
FIRE HYDRANT MAXIMUM COVERAGE PER
SPRINKLER IS 130 SOFT FOR STANDARD SPRAY
SPRINKLERS
File Name
Bldg Permit #10291
Address
8801 Astronaut Blvd
OVERHEAD PIPING PLAN I�
PROJECT NAME
PIE TRO'S PIZZERIA
8801 ASTRONAUT BLVD
CAPE CANAVERAL FLORIDA
DRAWN BY Chris J Lorton DATE September 25 2013
SPRKS ON JOB 17 SCALE As ( oted
APPROVALS LOCAL AUTHORIT(
CONTRACT NO SHEET NO i OF 1